J-NET Analog-Addressable Fire Alarm Control Panel

J-NET Analog-Addressable Fire Alarm Control Panel
J-NET FACP sub-panel
J-NET Analog-Addressable Fire Alarm Control Panel
J-NET FACP sub-panel

The J-NET Analogue-Addressable Fire Alarm Control Panel with networking capabilities is designed to facilitate the configuration of wide area fire alarm and detection systems. The J-NET FACP includes Main Panel and Sub-panel and has following functions:

  • receiving signals from connected addressable fire detectors and input-output devices,
  • processing messages from addressable I/O devices and producing control signals in the system outputs in accordance with programmed algorithms,
  • indication of Alarm, Fault, Disable states by sound and visual means,
  • indication of location of detected Fire/Fault alerts,
  • recording messages about Alarm, Fault, Disable states in the event log,
  • monitoring the system functional integrity and indication of any trouble,
  • supplying power to loop devices.
  • Features
  • Technical Data
  • Downloads
    • 1 to 3 detection loops per panel
    • 125 address per loop
    • Detection loops monitored for integrity
    • 2 Fire output relays (change over), 1 Fault relay (normally closed)
    • Open collector outputs for Fire, Fault and Pre-alarm remote indicators
    • 2 sounder outputs on Main Panel and Sub-panel (individually programmable)
    • History record, event log of 2000 entries (FIFO)
    • Backlit LCD display
    • Onboard keypad, PS/2 Keyboard
  • Main Control PanelSub-panel
    Main power supply100-264 V, 2,4 A, 50/60 Hz
    Backup power supply (sealed lead acid battery, not included)12 V, 7/12 A·h (2 batteries for every control panel)
    Max. current consumption2185 mA1955 mA
    Max. current consumption in idle mode1985 mA1755 mA
    Quiescent current (no devices)130 mA
    Loops1 to 3 loops, max. 275 mA per loop
    Auxiliary power supply output for powering external devices (2 outputs)Max. DC 230 mA (at 27,5 V) every output
    Sounder outputs (2 monitored outputs)Max. DC 400 mA (at 27,5 V) every output
    Fire relay (2 switching relay outputs)50 V, DC/AC 1 A, resistive load
    Fault relay (1 NC relay)50 V, DC/AC 1 A, resistive load
    Loop capacity125 address per loop
    Max. number of loops in the system96
    Zone capacity386 programmable zones
    Event log2000 entries
    Control panel communicationRS-485 bus (up to 1200 m)
    RS-232 output1 output
    Zone LED indication32 for Fire
    32 for Fault
    Enclosure dimensions (W х H х D), mm500 х 412 х 140
    Enclosure IP ratingIP30
    Enclosure materialSteel
    Weight (without batteries)≤ 11 kg≤ 10 kg
    Operating temperature0 °С to +40 °С
    HumidityUp to 93 % (no condensation / icing)
    Average service life10 years
  • Login or register to get access to full datasheets